Analysis of Furaldehyde Content of the Oil and its Diagnostic Value for Transformer Ageing
محل انتشار: چهاردهمین کنفرانس بین المللی برق
سال انتشار: 1378
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 2,532
فایل این مقاله در 10 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
PSC14_127
تاریخ نمایه سازی: 30 شهریور 1386
چکیده مقاله:
Electrical insulation paper has been aged under controlled conditions. The degradation rates were measured for cotton and Kraft paper in oil at three temperatures, 120-160oC. The furans produced during the ageing process were measured using High Performance Liquid Chromatography. The effect of oxygen and water on the production of furans was investigated. The relationship t Between the furan concentration in tho oil and the change of Degree of Polymerisation of the paper was also examined.
کلیدواژه ها:
نویسندگان
ood
N; tional Grid Company Engineering & Technology, Substations & Cables Kelvin Avenue, Leatherhead, Surrey, KT۲۲ ۷ST United Kingdom
Pahlavanpour
N; tional Grid Company Engineering & Technology, Substations & Cables Kelvin Avenue, Leatherhead, Surrey, KT۲۲ ۷ST United Kingdom
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :