Ventilated window: a solution to the synchronic improvement of energy saving and indoor air quality
محل انتشار: ششمین کنفرانس سالیانه انرژی پاک
سال انتشار: 1397
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 547
فایل این مقاله در 10 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
CLEANENERGY06_021
تاریخ نمایه سازی: 1 دی 1398
چکیده مقاله:
In this paper, the performances of the ventilated window in the energy saving and providing indoor air quality (IAQ) criteria were examined. The analytical zonal model coupled to airflow network model was used to evaluate the thermal performance of the system as well as the airflow rated induced. The simulation was done for an office located in Shiraz city. The results showed that the maximum monthly energy saving of 9.7% compared to the double-glazed window is obtained in August while the minimum value is achieved in March with -1.9% meaning a deterioration of using the ventilated window. The annual energy saving is 5.3%. Comparing the hourly airflow rate generated in the channel of the ventilated window with the indoor air quality standard of ASHRAE 62.1, the sufficient fresh air for IAQ is provided for 250 days of the year during the office working time. Furthermore, the parametric study focusing on the effect of the aspect ratio, channel thickness and opening size on the energy saving and IAQ was studied. The increase in the channel thickness and opening size enhances the energy saving and the IAQ indexes while the aspect ratio increase results in the energy saving and IAQ indexes reduction.
کلیدواژه ها:
نویسندگان
Farid Khalvati
Shiraz University of Technology, Shiraz, Iran
Amir Omidvar
Shiraz University of Technology, Shiraz, Iran