The Effects of Excitation Control Systems on Parallel Operation of DGs with the Main Grid

سال انتشار: 1386
نوع سند: مقاله ژورنالی
زبان: انگلیسی
مشاهده: 536

فایل این مقاله در 8 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

JR_JIAE-4-1_005

تاریخ نمایه سازی: 13 تیر 1396

چکیده مقاله:

This paper presents actual cases of steady reactive power oscillation of Distributed Generations (DGs) during parallel operation with the main grid. The cause of the problem was found to be the adverse effects of excitation system voltage regulation. It is shown, through preliminary investigation and detailed simulation studies, that how the excitation control system can be modified to overcome this problem. Onsite test results verify the analysis results and effectiveness of the remedial actions. Finally, general practical recommendations are offered for excitation control of synchronous generator-based DG, such that it performs properly, both in grid connected and islanding conditions.

نویسندگان

S. Kazemi

Department of Electrical Engineering Shrif University of Technology, Tehran, Iran

M. Parniani

Department of Electrical Engineering Shrif University of Technology, Tehran, Iran

M. Rasouli

Department of Electrical Engineering Shrif University of Technology, Tehran, Iran