Investigation of Electromagnetic Forces Affected by Short-Circuit Which Happens in Part of Transformer Winding
سال انتشار: 1397
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 499
فایل این مقاله در 8 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
TECCONF03_007
تاریخ نمایه سازی: 5 آبان 1397
چکیده مقاله:
When the short circuit faults are occur, larger amount of flux is diverted to the air outside the core. Thus, the leakage fluxes and the forces are increased. This paper is investigated radial and axial forces due to short circuit part of transformer winding. A 2-D model is considered and electromagnetic forces on different part of 25KVA transformer are displayed. We divided high voltage (HV) winding into 21 sections as winding of transformer model and make short-circuit of 0.5 percent of winding turn number. Electromagnetic forces are analyzed before short-circuit by finite element method and analytical method and then compared with each other and On the other hand, Magnetic flux densities and electromagnetic forces are analyzed in the manner of fault by finite element method (FEM). The results of short circuit forces are useful for transformer design
کلیدواژه ها:
نویسندگان
Alireza Shams
Department of Electrical and Computer Engineering, Faculty of Marvdasht, Technical and Vocational University (TVU), Fars
Esmaeil Zare
Department of Electrical and Computer Engineering, Faculty of Marvdasht, Technical and Vocational University (TVU), Fars
Vahid Fallahi
Department of Electrical and Computer Engineering, Faculty of Marvdasht, Technical and Vocational University (TVU), Fars