Islanding Detection of Synchronous Distributed Generation Based on Rate of Change of Direct and Quadratic Axes Quantities of Stator Current
سال انتشار: 1396
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 528
فایل این مقاله در 5 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
ELECONFK04_060
تاریخ نمایه سازی: 11 شهریور 1397
چکیده مقاله:
This paper presents a novel passive islanding detection method for synchronous distributed generation based on rate of change of direct quantity of stator current (dId /dt) and rate of change of quadratic quantity of stator current (dIq/dt) signals. The maximum changes magnitude of (dId/dt) and (dIq/dt) are continuously compared with the predetermined threshold values. If the both values are exceeds the threshold values, it is concluded that the islanding has occurred. Otherwise, it is considered as the non-islanding event. The proposed method has been evaluated in the presence of synchronous DG by MATLAB software. The simulation results indicate that the proposed method capable to identify the islanding rapidly and accurately even with zero non-detection zone (NDZ).
کلیدواژه ها:
passive method ، islanding detection ، direct and quadratic quantities of stator current ، synchronous DG
نویسندگان
Ali Rostami
Department of Electrical Engineering, South Tehran Branch University, Tehran-Iran /West Regional Electric Company, Kermanshah-Iran
Afshar Bali
West Regional Electric Company, Kermanshah-Iran
Asghar Khosroabadi
West Regional Electric Company, Kermanshah-Iran