Case study on corrosion of disulfide oil separator drum

سال انتشار: 1393
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 1,366

فایل این مقاله در 9 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

OGPCONF01_045

تاریخ نمایه سازی: 19 اردیبهشت 1395

چکیده مقاله:

We were studied a corrosion failure at liquefied petroleum gas (LPG) treatment unit in the second refinery of South Pars. Disulfide oil separator (DSO) drum wasinvestigated for corrosion failure. The study was performed on inspection reports as wanted shut downs. The results showed that the corrosion was occurred at 9 to 3 o clock area. Morphology of corrosion was as gouging. Maximum depth of gouging was 2.5 to 3 mm. More investigation showed that bad operation condition cause to decompose disulfides. Finally, the decomposed compounds cause corrosion

کلیدواژه ها:

نویسندگان

Reza Danaei Moghadam

Corrosion engineer, South Pars Gas Complex, Assaluie, Iran

Peyman Salaryan

Researcher, 2R inspection & Quality Services company, Tehran,Iran