A Novel Approach to Decaying DC offset Removal in Current Signals of Digital Relays

سال انتشار: 1393
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 1,175

فایل این مقاله در 5 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

PSC29_104

تاریخ نمایه سازی: 6 آذر 1393

چکیده مقاله:

In this paper a new method for estimation and removal of decaying dc offset from fault current signal using Least Median of Squares Regression (LMSR) method is proposed. Fault currents tend to include a dc decaying component. This component decreases the accuracy and speed of the protective relaying operation. The proposed method can estimate and eliminate the dc decaying component from fault current signals after one cycle from the fault instant. The dc decaying magnitude and time constant are estimated exactly during one cycle. The dc decaying component is eliminated by subtracting the dc value at each sampling instant. To verify the performance of the proposed method, we performed a dc component estimation test and distance protection test using PSCAD/EMTDC. The results of the PSCAD/EMTDC simulation showed that the proposed method can estimate dc components exactly from fault currents and can be applied to digital protection relays for phasor extraction.

کلیدواژه ها:

Digital relaying ، Decaying Dc offset ، DC estimation ، Least Median of Squares Regression Method

نویسندگان

Zahra Moravej

Electrical Engineering Department Semnan University Semnan, Iran

Seyed Reza Ebrahimi

Electrical Engineering Department Hadaf University Sari, Iran

Sajad Bagheri

Electrical Engineering Department Semnan University Semnan, Iran