An Alternative Technique to Assess Transformer Dry-out Process
سال انتشار: 1393
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 1,275
فایل این مقاله در 13 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
ITCE01_008
تاریخ نمایه سازی: 6 آبان 1393
چکیده مقاله:
Frequency Response Analysis (FRA) has been implemented since the last decade as an accurate method in transformer mechanical defectrecognition. Recent studies revealed that this method is quite effective to trace the transformer insulation behavior. This study has concentrated on FRA capability to access transformer winding dry-out process. To this end, a single phase glassy model transformer involving concentric LV and HV windings is fabricated and taken as a test object. FRA spectra for HV and LV windings of the test object are recorded for wet and dry condition of the paper insulation. Karl-Fischer Titration (KFT) is employed to determine the moisture content ofthe oil, and paper insulation humidity is derived using equilibrium curves. Deviation in FRA spectra for HV and LV windings before and after dry-out process are elaborated and total capacitance variations due to the moisture diffusion through transformer windings are calculated and discussed.
کلیدواژه ها:
نویسندگان
Mehdi Bagheri
School of EE&T, University of New South Wales Sydney, NSW ۲۰۵۲, Australia
B.T Phung
School of EE&T, University of New South Wales Sydney, NSW ۲۰۵۲, Australia
Trevor Blackburn
School of EE&T, University of New South Wales Sydney, NSW ۲۰۵۲, Australia
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :