Evaluating the Possibility of Utilizing the Waste Heat of Hot Water before the Cooling Towers Based on Phase Change Material
سال انتشار: 1403
نوع سند: مقاله ژورنالی
زبان: انگلیسی
مشاهده: 87
فایل این مقاله در 16 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
JR_IJCCE-43-7_023
تاریخ نمایه سازی: 17 خرداد 1404
چکیده مقاله:
Today, efficient energy use and minimizing waste are crucial. In power plants, hot water with high thermal energy enters a cooling tower, requiring significant water consumption for cooling. In the current research, the possibility of exploiting the thermal energy of hot water between the turbine and the cooling tower has been investigated using shell and tube heat exchangers where the shell is filled with Phase Change Materials (PCM). This research investigates the temperature reduction of the hot water temperature entering the cooling tower and the possibility of using the thermal energy of the hot water entering the cooling tower. Two approaches are included: a PCM-based heat exchanger for thermal storage and a heat exchanger to reduce hot water temperature without energy storage capability. Paraffin, a phase change material, is placed between the tube and shell in a heat exchanger, where hot water flows through the tube. The enthalpy-porosity model simulates phase change. Outlet hot water temperature, volume fraction changes, and paraffin temperature in finned and non-finned tubes are compared in different conditions. Also, fines are installed on the shell side to investigate the heat transfer enhancement. Results suggest that with an insulated shell, a thermal storage system should use a heat sink (cold water) to absorb released heat during paraffin solidification. The insertion of fins increases the paraffin phase change rate to about ۱۰۰% which reduces the required time to complete melt from ۱۰ to ۴ hours, thus enhancing the heat transfer rate significantly. Results indicate that in a colder climate with temperatures significantly below the melting point, non-insulated heat exchangers can maintain steady performance which can cause a steady two-phase regime of PCM (steady liquid volume fraction of about ۰.۵) and keep the shell temperature constant over time. Finally, it could reduce the hot water temperature that enters the cooling tower by about ۶ degrees.
کلیدواژه ها:
Phase change material (PCM) ، Enthalpy-Porosity modeling ، heat exchanger ، Water wasting ، finite volume
نویسندگان
Reza Bemani
Department of Mechanical Engineering, Bushehr Branch, Islamic Azad University, Bushehr, I.R. IRAN
Zahra Hashemi
Department of Mechanical Engineering, Bushehr Branch, Islamic Azad University, Bushehr, I.R. IRAN
Maysam Gholampour
Department of Mechanical Engineering, Bushehr Branch, Islamic Azad University, Bushehr, I.R. IRAN
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :