Application of Relaxation Distribution Function in Diagnostic of Power Transformer Insulation
محل انتشار: نوزدهمین کنفرانس بین المللی برق
سال انتشار: 1383
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 2,305
فایل این مقاله در 6 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
PSC19_247
تاریخ نمایه سازی: 12 آذر 1385
چکیده مقاله:
In this paper the relaxation distribution function, which is obtained from measuring the polarization and depolarization current (PDC) on oil-pressboard samples, will be presented. The samples have been aged at 115 °C with Fe, Cu and Zn contents as catalyst in order to simulate the stress conditions. Four samples have been aged for 250, 500, 1000, 2000 hours. Tests have been made also on four moisturized samples. Depolarization current curves are decomposed to basic relaxation functions. The results obtained show classification of samples to dry and wet is possible. Also, the quality of oil can be determined from the relaxation distribution function. Aging state of the samples has an impact on the measuring result and the degree of aging of the insulation can be distinguished.
کلیدواژه ها:
نویسندگان
Amir Abbas Shayegani
University of Tehran, Department of Electrical Engineering, Iran
Hossein Mohseni
University of Tehran, Department of Electrical Engineering, Iran
Hossein Borsi
University of Hannover, Institute of Electric Power System (Schering-institute), Germany
Ernst Gockenbach
University of Hannover, Institute of Electric Power System (Schering-institute), Germany
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :