Mitigation of Voltage Sags in a Sample Distribution System Using Flexible D-STATCOM
- سال انتشار: 1390
- محل انتشار: نوزدهمین کنفرانس مهندسی برق ایران
- کد COI اختصاصی: ICEE19_361
- زبان مقاله: انگلیسی
- تعداد مشاهده: 1523
نویسندگان
Student Member, IEEE
Student Member, IEEE
Member, IEEE
Member, IEEE
چکیده
This paper proposes a Flexible D-STATCOM (Distribution STATIC Compensator) and its new controller system, in IEEE 13-bus industrial distribution system, that be able to both mitigate all types of series faults (open-circuit or open conductor faults) and operate as a Distributed Generation (DG), when it supplies power to sensitive loads while the main utility source is disconnected (i.e. it is under islanded operating condition). Thus D-STATCOM operates same as a Flexible DG (FDG) and consequently, it is called Flexible D-STATCOM (FD-STATCOM). In this paper, the 12-pulse FD-STATCOM configuration with IGBT is designed and the graphic based models of the FD-STATCOM are developed using the PSCAD/EMTDC electromagnetic transient simulation program. The reliability and robustness of the control schemes in the system response to the voltage disturbances caused by series faults and islanded operating condition are obviously proved in the simulation results.کلیدواژه ها
Custom Power, FD-STATCOM, Voltage Sags, Energy Storage Systems, Test System, Islanding Conditionمقالات مرتبط جدید
اطلاعات بیشتر در مورد COI
COI مخفف عبارت CIVILICA Object Identifier به معنی شناسه سیویلیکا برای اسناد است. COI کدی است که مطابق محل انتشار، به مقالات کنفرانسها و ژورنالهای داخل کشور به هنگام نمایه سازی بر روی پایگاه استنادی سیویلیکا اختصاص می یابد.
کد COI به مفهوم کد ملی اسناد نمایه شده در سیویلیکا است و کدی یکتا و ثابت است و به همین دلیل همواره قابلیت استناد و پیگیری دارد.