ACCURATE EQUIVALENT CIRCUIT MODEL OF GROUNDING HORIZONTAL ELECTRODES BURIED IN HORIZONTALLY TWO-LAYERED SOIL

  • سال انتشار: 1398
  • محل انتشار: هفتمین کنفرانس منطقه ای سیرد
  • کد COI اختصاصی: CIRED07_023
  • زبان مقاله: انگلیسی
  • تعداد مشاهده: 142
دانلود فایل این مقاله

نویسندگان

Sajad MEHRABI

MSC student from Arak University-Iran

Vahid AGHAJANI

MSC student from Arak University-Iran

Saeed Reza OSTADZADEH

Assistance Professor from Arak University-Iran

چکیده

In this paper, we investigate validity of RLC equivalent circuit for transient analysis of grounding horizontal electrodes buried in horizontally two-layered soils. The simulationresults show that such an equivalent circuit is violated at high frequencies created by lightning strokes. Hence, in this paper, a new equivalent circuit is proposed. In the new circuit model, vector fitting method (VF) is combined with finite element method (FEM) so that a wide-band equivalent circuit is obtained. Such a model is useful for lightning performance of power systems.

کلیدواژه ها

horizontally two-layered soil; horizontal electrode; lightning stroke, vector fitting.