High impedance fault detection: Discrete wavelet transform and fuzzy function approximation

سال انتشار: 1392
نوع سند: مقاله ژورنالی
زبان: انگلیسی
مشاهده: 670

فایل این مقاله در 11 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

JR_JADM-2-2_005

تاریخ نمایه سازی: 9 اسفند 1393

چکیده مقاله:

This paper presents a method including a combination of the wavelet transform and fuzzy function approximation (FFA) for high impedance fault (HIF) detection in distribution electricity network. Discrete wavelet transform (DWT) is used in this paper as a tool for a signal analysis and after studying differenttypes of mother signals, detailed types and feeder signal, the best case is selected. In the next step, the DWT is used to extract the features. The extracted features are used as the FFA Systems inputs. The FFA system uses the input-output pairs to create a function approximation of the features. The FFA system is able toclassify the new features. The combined model is used to model the HIF. This combined model has the high ability to model different types of HIF. In the proposed method, different kind of loads including nonlinear and asymmetric loads and HIF types are studied. The results show that the proposed method has high capability to distinguish between no fault and HIF states accurately.

نویسندگان

m banejad

Electrical Engineering Department, Shahrood University of Technology, Shahrood, Iran

Hassan ijadi

Electrical Engineering Department, Shahrood University of Technology, Shahrood, Iran