Evaluating the Possibility of Utilizing the Waste Heat of Hot Water before the Cooling Towers Based on Phase Change Material
- سال انتشار: 1403
- محل انتشار: Iranian Journal of Chemistry and Chemical Engineering، دوره: 43، شماره: 7
- کد COI اختصاصی: JR_IJCCE-43-7_023
- زبان مقاله: انگلیسی
- تعداد مشاهده: 237
نویسندگان
Department of Mechanical Engineering, Bushehr Branch, Islamic Azad University, Bushehr, I.R. IRAN
Department of Mechanical Engineering, Bushehr Branch, Islamic Azad University, Bushehr, I.R. IRAN
Department of Mechanical Engineering, Bushehr Branch, Islamic Azad University, Bushehr, I.R. IRAN
چکیده
Today, efficient energy use and minimizing waste are crucial. In power plants, hot water with high thermal energy enters a cooling tower, requiring significant water consumption for cooling. In the current research, the possibility of exploiting the thermal energy of hot water between the turbine and the cooling tower has been investigated using shell and tube heat exchangers where the shell is filled with Phase Change Materials (PCM). This research investigates the temperature reduction of the hot water temperature entering the cooling tower and the possibility of using the thermal energy of the hot water entering the cooling tower. Two approaches are included: a PCM-based heat exchanger for thermal storage and a heat exchanger to reduce hot water temperature without energy storage capability. Paraffin, a phase change material, is placed between the tube and shell in a heat exchanger, where hot water flows through the tube. The enthalpy-porosity model simulates phase change. Outlet hot water temperature, volume fraction changes, and paraffin temperature in finned and non-finned tubes are compared in different conditions. Also, fines are installed on the shell side to investigate the heat transfer enhancement. Results suggest that with an insulated shell, a thermal storage system should use a heat sink (cold water) to absorb released heat during paraffin solidification. The insertion of fins increases the paraffin phase change rate to about ۱۰۰% which reduces the required time to complete melt from ۱۰ to ۴ hours, thus enhancing the heat transfer rate significantly. Results indicate that in a colder climate with temperatures significantly below the melting point, non-insulated heat exchangers can maintain steady performance which can cause a steady two-phase regime of PCM (steady liquid volume fraction of about ۰.۵) and keep the shell temperature constant over time. Finally, it could reduce the hot water temperature that enters the cooling tower by about ۶ degrees.کلیدواژه ها
Phase change material (PCM), Enthalpy-Porosity modeling, heat exchanger, Water wasting, finite volumeاطلاعات بیشتر در مورد COI
COI مخفف عبارت CIVILICA Object Identifier به معنی شناسه سیویلیکا برای اسناد است. COI کدی است که مطابق محل انتشار، به مقالات کنفرانسها و ژورنالهای داخل کشور به هنگام نمایه سازی بر روی پایگاه استنادی سیویلیکا اختصاص می یابد.
کد COI به مفهوم کد ملی اسناد نمایه شده در سیویلیکا است و کدی یکتا و ثابت است و به همین دلیل همواره قابلیت استناد و پیگیری دارد.