Reduction of voltage violation in distribution network with low rises in power losses and tap position volatility

  • سال انتشار: 1390
  • محل انتشار: نوزدهمین کنفرانس مهندسی برق ایران
  • کد COI اختصاصی: ICEE19_380
  • زبان مقاله: انگلیسی
  • تعداد مشاهده: 1109
دانلود فایل این مقاله

نویسندگان

Meysam Najafi

Iran University of Science and Technology

Shahram Jadid

Iran University of Science and Technology

چکیده

this paper discusses the problem of voltage rise caused by connecting distributed generation to the weak distribution networks. The method presented in this paper is combination of power factor controller (PFC) with reactive power controller (Q*) to reduce the variation of voltage and OLTC transformer’s tap position. This method uses a series of conditions to switch intelligently between reactive power and power factor control modes. In order to achieve better and more accurate results, proposed method is implemented in radial feeder that equipped with OLTC transformer and stochastic load and generation. Result of simulations has demonstrated that the proposed method has a good performance in reduce the variation of voltage, tap position and amount of losses in the feeder.

کلیدواژه ها

Distributed generation, distribution networks, stochastic load and generation, voltage rise, voltage control